ALSECURE® H07Z1-K (AS), 1x25 mm², black

Description

Description

Standards

  • Product
    EN 50525-3-31; EN 50575; IEC 60228; UNE 21022; UNE 211002
  • Installation
    NF C15-100
  • Test
    EN 50266-2-4; EN 50267-2-2; EN 50399; EN 60754-2; IEC 60332-1-2; IEC 60332-3-24; IEC 61034-2; NF C32-070/C2; UNE EN 50267-2-3 ; UNE-EN 50265-2-1

Application

Nexans H07Z1-K PROTECT Type 2 (AS) is designed for protected low-voltage fixed installations. It is suitable for the wiring of electrical panels, switchboards, control equipment, electrical apparatus and circuits installed in conduits or trunking.
Its Class 5 flexible copper conductor facilitates installation in applications requiring enhanced flexibility, such as compact switchboards, industrial and commercial cabinets, internal equipment wiring and colour-coded circuits.
The halogen-free, low-smoke insulation makes it particularly suitable for installations in buildings where fire safety requirements are critical, including public buildings, high-rise buildings, residential complexes, schools, healthcare facilities, commercial premises and protected industrial environments.

Installation

Nexans H07Z1-K PROTECT Type 2 (AS) is intended for protected indoor fixed installations in conduits, ducts, trunking systems, raceways, skirting-board trunking, mouldings or similar closed systems, either surface-mounted or concealed, in accordance with applicable installation practices and regulations. It may also be used for the internal wiring of electrical panels, switchboards, electrical apparatus and control equipment, provided compatibility with terminals and applicable wiring rules is ensured. It is not intended for direct outdoor installation, direct burial, immersion, or for mobile applications or installations subject to repeated flexing.

Recommended installation:

  • Minimum installation temperature: +5 °C
  • Minimum bending radius: 4 × D for fixed installation
  • Maximum pulling force: 50 N/mm² of copper cross-section

Encuentra este producto en EASYCALC™

New cardboard packaging for H07V-K and H07Z1-K

Color code for Nexans Alsecure H07Z1-K cross-section

Cable colors available

-

-

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Insulation
Halogen free, TI 7 acc. EN 50363-7
Conductor flexibility
Flexible class 5
Conductor shape
Circular
Insulation colour
Black
With Green/Yellow core
No
With smaller neutral conductor
No
Halogen free
Yes
Lead free
Yes

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
25 mm²
Approximate weight
25 kg/km
Neutral conductor section (when smaller)
- mm²
Number of cores
1
Outer Diameter
- mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
- Ohm/km
Maximum operating voltage
750 V
Permissible current rating in open air
- A
Test voltage
2500 V

Mechanical characteristics

Mechanical characteristics

Maximum tensile strength
50 N/mm2
Cable flexibility
Flexible
Mechanical resistance to impacts
Low

Usage characteristics

Usage characteristics

Fire retardant
EN 50399; EN 60332-1-2
Flame retardant
EN 50265-2-1
Smoke density
IEC 61034-2
Bending factor when laying
4 (xD)
Max. conductor temperature in service
70 °C
Operating temperature, range
-5 ... 70 °C
Short-circuit max. conductor temperature
160 °C
Chemical resistance
Restricted to oil, acid & base
Maximum operating temperature
70 °C
Packaging
Coil
Water proof
Limited
Weather resistance
Restricted, not ozon stable

Resources

Resources

Documentation

H07Z1-K PEP pdf — 4.3 MB
CMC H07Z1-K pdf — 778.9 kB

Current capacity table PVC insulation multicore three phase

Conductor cross-section A2 - Multi-core cable in conduit in a thermally insulated wall B2 - Multi-core cable in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground E - Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
25.0 68.0 53.0 80.0 62.0 96.0 73.0 82.0 64.0 92.0 69.0 101.0 78.0

Current capacity table PVC insulation multicore single phase

Conductor cross-section A2 - Multi-core cable in conduit in a thermally insulated wall B2 - Multi-core cable in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground E - Multi-core cable in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
25.0 75.0 58.0 90.0 71.0 112.0 83.0 99.0 77.0 110.0 82.0 119.0 89.0

Current capacity table PVC insulation single core three phase

Conductor cross-section A1 - Insulated conductors in conduit in a thermally insulated wall B1 - Insulated conductors in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground F - Single-core flat cables, touching in free air Ft - Single-core trefoil cables, touching in free air G - Single-core horizontal spaced Gv - Single-core flat vertical spaced
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
25.0 73.0 57.0 89.0 70.0 96.0 73.0 82.0 64.0 92.0 69.0 114.0 87.0 110.0 146.0 84.0 112.0 130.0 99.0

Current capacity table PVC insulation single core single phase

Conductor cross-section A1 - Insulated conductors in conduit in a thermally insulated wall B1 - Insulated conductors in conduit on a wooden wall C - Single-core or multi-core cable on a wooden wall D1 - Single-core or Multi-core cable in ducts in the ground D2 - Single-core or Multi-core cables designed to be buried directly in the ground F - Single-core flat cables, touching in free air
mm² Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
25.0 80.0 63.0 101.0 79.0 112.0 83.0 99.0 77.0 110.0 82.0 131.0 98.0

Selling & delivery Information

Ink jet marking
USE - HAR- ALSECURE H07Z1-K (AS) TYPE 2 AENOR PLANT N° NEXANS – DAY YEAR

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close