ALSECURE-K 1X10 Brown GL8000
Certifications and labels
ALSECURE-K 1X10 Brown GL8000
Nexans H07Z1-K PROTECT Type 2 (AS) is a 450/750 V halogen-free, flexible single-core insulated conductor with enhanced fire performance, compliant with EN 50525-3-31. Designed as an alternative to PVC-insulated H07V-K wiring, it is intended for protected fixed installations where both high wiring flexibility and fire safety are key selection criteria.
Its Class 5 flexible copper conductor facilitates installation in electrical panels, switchboards, trunking systems, conduits and control equipment. With its CPR classification Cca-s1,d1,a1, it meets the enhanced fire reaction requirements of sensitive buildings such as hospitals, airports, shopping centres, cinemas, schools and high-rise buildings.
Benefits
- Fire Safety: Provides up to five times greater visibility than a standard PVC-insulated wire thanks to its low smoke emission. Its halogen-free formulation limits the acidity of emitted gases and helps reduce fire propagation.
- Ease of Installation: Features a Class 5 flexible copper conductor and insulation with enhanced sliding properties, making pulling, bending and wiring easier in electrical panels, cabinets, trunking systems and conduits.
- Reduced Carbon Footprint: Environmental data available through the PEP Ecopassport® programme.
- Nexans ref. : 10093179
- Country ref. : 102 - 103 - 336
- EAN : 3427500011744
Description
Description
Standards
-
ProductEN 50525-3-31; EN 50575; IEC 60228; UNE 21022; UNE 211002
-
InstallationNF C15-100
-
TestEN 50266-2-4; EN 50267-2-2; EN 50399; EN 60754-2; IEC 60332-1-2; IEC 60332-3-24; IEC 61034-2; NF C32-070/C2; UNE EN 50267-2-3 ; UNE-EN 50265-2-1
Application
Nexans H07Z1-K PROTECT Type 2 (AS) is designed for protected low-voltage fixed installations. It is suitable for the wiring of electrical panels, switchboards, control equipment, electrical apparatus and circuits installed in conduits or trunking.
Its Class 5 flexible copper conductor facilitates installation in applications requiring enhanced flexibility, such as compact switchboards, industrial and commercial cabinets, internal equipment wiring and colour-coded circuits.
The halogen-free, low-smoke insulation makes it particularly suitable for installations in buildings where fire safety requirements are critical, including public buildings, high-rise buildings, residential complexes, schools, healthcare facilities, commercial premises and protected industrial environments.
Installation
Nexans H07Z1-K PROTECT Type 2 (AS) is intended for protected indoor fixed installations in conduits, ducts, trunking systems, raceways, skirting-board trunking, mouldings or similar closed systems, either surface-mounted or concealed, in accordance with applicable installation practices and regulations. It may also be used for the internal wiring of electrical panels, switchboards, electrical apparatus and control equipment, provided compatibility with terminals and applicable wiring rules is ensured. It is not intended for direct outdoor installation, direct burial, immersion, or for mobile applications or installations subject to repeated flexing.
Recommended installation:
- Minimum installation temperature: +5 °C
- Minimum bending radius: 4 × D for fixed installation
- Maximum pulling force: 50 N/mm² of copper cross-section
Encuentra este producto en EASYCALC™
New cardboard packaging for H07V-K and H07Z1-K
Color code for Nexans Alsecure H07Z1-K cross-section
Cable colors available
-
-
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Dimensional characteristics
Dimensional characteristics
Electrical characteristics
Electrical characteristics
Mechanical characteristics
Mechanical characteristics
Usage characteristics
Usage characteristics
Resources
Resources
Documentation
Current capacity table PVC insulation multicore three phase
| Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 39.0 | 31.0 | 46.0 | 36.0 | 57.0 | 44.0 | 50.0 | 39.0 | 54.0 | 0.0 | 60.0 | 46.0 |
Current capacity table PVC insulation multicore single phase
| Conductor cross-section | A2 - Multi-core cable in conduit in a thermally insulated wall | B2 - Multi-core cable in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | E - Multi-core cable in free air | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 43.0 | 33.0 | 52.0 | 41.0 | 63.0 | 49.0 | 60.0 | 47.0 | 64.0 | 0.0 | 70.0 | 54.0 |
Current capacity table PVC insulation single core three phase
| Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | Ft - Single-core trefoil cables, touching in free air | G - Single-core horizontal spaced | Gv - Single-core flat vertical spaced | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 42.0 | 32.0 | 50.0 | 39.0 | 57.0 | 44.0 | 50.0 | 39.0 | 54.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Current capacity table PVC insulation single core single phase
| Conductor cross-section | A1 - Insulated conductors in conduit in a thermally insulated wall | B1 - Insulated conductors in conduit on a wooden wall | C - Single-core or multi-core cable on a wooden wall | D1 - Single-core or Multi-core cable in ducts in the ground | D2 - Single-core or Multi-core cables designed to be buried directly in the ground | F - Single-core flat cables, touching in free air | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| mm² | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 10.0 | 46.0 | 36.0 | 57.0 | 44.0 | 63.0 | 49.0 | 60.0 | 47.0 | 64.0 | 0.0 | 0.0 | 0.0 |
Selling & delivery Information
Ink jet marking
USE - HAR- ALSECURE H07Z1-K (AS) TYPE 2 AENOR PLANT N° NEXANS – DAY YEAR
Declaration of Performance
- Declaration of Performance n° : 1000150-FRAU
- Certification Date : 6/23/26
- AVCP (Assessment and Verification of Constancy of Performance) : System 1+
- Notified body : NB 099
- Declared performance : Cca-s1b,d1,a1